Physical Description
|
|
| Enclosure Dimensions |
25.4 x 20.3 x 15.2 cm (10 x 8 x 6 in.) |
| Enclosure Rating |
NEMA 4X |
| Display |
Liquid Crystal |
|
|
Electrical Requirements
|
|
| Operating Power |
85 to 265 VAC or 100 to 370 VDC (20 to 70
VDC optimal) |
| Relay Contact Rating |
0.1 Amperes, 125 VDC resistive |
| Internal Heater |
100 Watts, 100 to 125 VAC only |
| Grounding |
Must be bonded to circuit breaker |
| DC Isolation |
1500 Volts |
|
|
Temperature Ratings
|
|
| Ambient Maximum Temperature |
60° C (140° F) |
| Ambient Minimum Temperature |
-50° C (-58° F) |
| SF6
Temperature Range |
-50° C to +60° C (-58° F to +140° F) |
| Temperature Scales Available |
Celsius and Fahrenheit |
|
|
Pressure Ratings
|
|
| SF6
Pressure Absolute Maximum |
400 psia (27.6 Bar) |
| SF6
Pressure Range |
0 to 150 psia (0 to 10.3 Bar) |
| Pressure Scales Available |
psi, bar, kg/cm2, MPa |
| Pressure Port Fittings |
1/4 inch tubing |
|
|
Density Functions
|
|
| Density % Range |
0 to 200% |
| Density Accuracy |
+/- 1% |
| Humidity Range |
0 to 100% (non-condensing) |
| Nitrogen (CF4) Content
Range |
0 to 100% |
| SF6
Normalized Temperature Range |
10° C to 40° C (50° F to 104° F) |
| SF6
Liquefaction Proximity Warning |
2 to 6 C° (4 to 11 F°) above liquefaction |
|
|
Hardware
|
|
Temperature Sensors
|
|
|
Materials |
Brass |
|
Mounting |
SF6 tank surface
mount |
|
Cable Run |
5 meters (16.4 feet) |
| Pressure
Transducers
|
|
|
Materials |
316 Stainless steel |
|
Mounting |
Bulkhead |
|
Cable Run |
None |
|
Port Fitting |
1/4 inch tubing |
|
|
Communications
|
|
| RS-232 Ports |
1 |
| RS-485 Ports |
1 |
| Fiber Optics |
None |
| Baud Rate |
1200 to 19.2 kbps |